Clamping Zones
The following clamping zones aims to illustrate the areas for correct placement of mounting points for current WINAICO Products. Please be aware that the images are not to scale and accurate measurement is required during installation.
Design Load = Test Load/1.5
WST375-MG and WST370-MG Full Black

Test Loading Pressure
Long Side Mounting:
- Front (Push): 5400 Pa
- Back (Pull): 3600 Pa
Short Side Mounting:
- Front (Push): 2400 Pa
- Back (Pull): 2400 Pa
WST333-MG

Test Loading Pressure
Long Side Mounting:
- Front (Push): 5400 Pa
- Back (Pull): 3600 Pa
Short Side Mounting:
- Front (Push): 2400 Pa
- Back (Pull): 2400 Pa
Clamping Zones
WINAICO modules are suitable for both vertical and horizontal installation methods due to their high degree of stability. The modules must be clamped in place at a minimum of 4 points. The modules must always be installed with the junction box either parallel with the ground if mounted horizontally, or at the top of a panel if situated vertically (see image below for reference).
If you have any questions regarding the mounting specified or require clarification, call us at 8091 277.

Mounting Clamps
The middle clamps can be used as spacers between the module rows when mounting the modules. To avoid any possible stresses and failure to comply with dimensions, a gap should be maintained between the module rows. WINAICO recommends a gap of approximately 2 cm but please refer to your mounting systems installation manuals.
For aesthetic reasons we recommend using black clamps for mounting our module series with black anodised frame and black backsheet. Do not touch live terminals with bare hands, and always use insulated tools for electrical connections.

Shortcut to other sections of the Installation Manual
This online tool is to provide installers with a more accessible summary of our WINAICO Installation Manual. Information provided should act as a guide only. If there is confusion, the PDF Installation Manual must be the main source for clarification.